Technical Specifications
Input (DC)
Recommended maximum input power of photovoltaic systems 37500 W
Max. input voltage of photovoltaic systems 1100 V
Startup input voltage 250 V
Nominal input voltage 600 V
MPP voltage range 200 V – 1000 V
Number of independent MPP inputs 3
Number of photovoltaic strings per MPP 2
Maximum input current per MPP tracker 26 A
Maximum short-circuit current for one MPP tracker 32 A
Output (AC)
Nominal output power of AC 25000 W
Max. total output power of AC 27700 VA
Nominal AC voltage (range) 220/380 V, 230/400 V (340-440 V)
Max. output current 40 A
AC grid frequency 50 Hz / 60 Hz
AC grid frequency range 45 – 55 Hz / 55 – 65 Hz
Total Harmonic Distortion (THD) < 3 % (at nominal power)
Adjustable power factor 0.8 leading – 0.8 lagging
Type of AC grid connection 3 Ph + N + PE
Efficiency
Maximum efficiency 98.8%
European efficiency 98.5%
MPPT efficiency 99.9%
Protection Devices
Grid monitoring yes
DC reverse polarity protection yes
AC short-circuit protection yes
Insulation resistance monitoring yes
Surge protection DC Type II / AC Type II
Ground fault monitoring yes
DC switch yes
String monitoring yes
Arc Fault Circuit Interrupter (AFCI) Optional
Anti-islanding protection yes
Residual current monitoring unit yes
General Data
Dimensions (W*H*D) 580*435*230 mm
Weight 29.5 kg
Topology Transformerless
Protection degree IP66
Night power consumption < 1 W
Operating temperature range -25 °C to +60 °C
Permissible relative humidity range (non-condensing) 0% – 100%
Cooling method Intelligent air cooling
Max. operating altitude 4000 m
Display OLED + LED / Wi-Fi + app
Interfaces RS-485 / USB
Additional interfaces Wi-Fi / GPRS / RF / LAN
DC connection H4 / MC4 (optional)
AC connection Cable entry + terminal block
Certification CE, VDE0126, Greece, EN50549, C10/C11, UTE C 15-712, IEC62116, IEC61727, IEC 60068, IEC 61683, CEI0-21, CEI0-16, N4105, Generator TOR G98/G99, G100, AS/NZS 3100, AS4777, UNE217001, UNE206007, PO12.2, KSC8565
Warranty:
The warranty for the voltage converter (inverter) is valid from the moment we (the seller) receive the serial number of the inverter, the purchase invoice, and the certificate from a certified electrician regarding the installation:
1) Lightning protection and surge protector (at the input)
2) Lightning protection (between solar panels and inverter)
3) DC switch between panels and inverter
4) Special grounding for solar panels, separate from the house grounding.
A 5-year (60-month) manufacturer's warranty begins on the day of purchase but takes effect only after the provision of these documents.
Note: Lightning strike is not a valid warranty case; it is classified as an insurance case.